xxxxxxxxxx CS2700/4700 Controllers Technical Reference_________________________________________
____________________________________________________________________________________________
Page 44 39-30-43083
SPECIAL APPLICATION: PFCS
(Ethernet or Terminal Server)
Important note:
CCM1.12 adds the ability to configure PFCS without the need to enter
into the console for units with a keypad/display. The CCM’s SW2 (2
nd
dip switch) can
force PFCS to be enabled. A special menu will then be available which will permit all of the
PFCS configurations.
Setting up to Link to a PFCS Host on Ethernet
1. Type “ipconfig +pfcs” to enable the PFCS client in the CS47XX/2700 Controller.
2. Type “pfcs mode ethernet” to configure PFCS for Ethernet operation
3. Use the “pfcs addr <ip addr>” and “pfcs port <port> “ to enter the PFCS server info.
4. See below for details in using the Barcode/Buffer or Custom Machine-ID options.
5. When complete be sure to use the “pfcs commit” command
6. Use the “pfcs +diag” command to assist in debugging
Setting up to Link to a PFCS Host on Terminal Server (RS232)
Asynch Daughter
(Attached to CCM)
Location of 25Pin-D
PFCS Terminal Server connector
1. Verify the controller has the add-on Asynch Daughter board & DB25 connector on the enclosure
2. Connect the DB25 cable from the PFCS Terminal Server to the controller
3. Type “ipconfig +pfcs” to enable the PFCS client in the controller
4. Type “pfcs mode terminalserver” to configure the PFCS client for (RS232)
5. See “pfcs ?” for details to set one of several options (ACK timeouts, Retries & other options)
6. When settings are complete type “commit” to save the settings
7. You can use the “pfcs start” or “pfcs stop” command although on power up PFCS will start auto.
Using Barcodes, Buffering and Machine IDs with PFCS
In order for the “avi” or “vin” data to be included in the packets to PFCS, the Model-Number or Part-
ID functions must be enabled with VS “system settings.”
NOTE:
?
PFCS buffering will not work unless either the “avi” or “vin” is
enabled. Also, the TCM may need to be set up for “VIN” history
mode with the VS “system settings” program (for model number
applications).
When using the “+psetid”, the Machine ID will be derived from the first four characters of the TCM’s parameter set
name that ran the cycle. VS must be used to establish parameter set names etc.