Chicago Pneumatic SD25 Manuel d'instructions Page 31

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 57
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 30
_____________________________________________________
CS4100/2100 Controllers Technical Reference
____________________________________________________________________________________________
September 2005 Page 29
Determining INPUT Sources
It is possible that INPUTS can enter into the single-channel CS4700 Controller from several sources.
Below is a list of some potential sources and their relative priority.
1. VsSetup assignments
a. Tool switches
b. Digital inputs (via a 19-pin connector etc.)
c. Auto-increment or barcode-based pset selections
2. Ford specific I/O (but only if the Ford interface is enabled via the console port)
3. Keypad pset selection (if a keypad is resident and enabled by default or via the console)
4. Fieldbus (which must be enabled by “defaults” via keypad or console)
Note that if no keypad is present (Defaults should be set via the console)
5. OPC inputs via Visual Supervisor/Applicaton programs
NOTE:
?
Enabling Fieldbus will block all INPUTS from OPC.
Examples:
You want to start the tool via Fieldbus. Set Default#1 below.
NOTE:
?
If VsSetup is run and “Cycle-On” is mapped to a tool trigger or
an input, it will then override the Fieldbus input.
You want to start the tool via OPC. Set Default#3 below. You must run VsSetup and unmap the
cycle-On input from the tool switch.
DEFAULTS INPUT Mapping from the Keypad (or RS-232 Console)
In order to initiate a CS47XX/2700 Controller to operate without using VS, several “Default” modes
have been provided. These can be selected via the Main Menu screen or by invoking the console
“Default” command. The Default selections allow the user to select the source of the pset-selects and
the location from which the tool will be controlled. The 4 selections are:
DEFAULT#
P
arameter Set select
Tool Running control
1
Fieldbus Fieldbus
2
Fieldbus Operator switches on tool
3
DCM physical I/O (or OPC) Operator switches on tool (or OPC)
4
Keypad Operator switches on tool
IMPORTANT
NOTE:
?
Selecting Default 1 or 2 (Fieldbus) will block any OPC changes. This
is important if VS is connected to a system running any Fieldbus I/O.
Also, Default #1 is SUGGESTED for any variations of Fieldbus
control, such as “Cycle-enable” from the PLC but the operator
wants to run the tool from the tool switches etc.
Vue de la page 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 56 57

Commentaires sur ces manuels

Pas de commentaire